Installation of VLT 8452-8652 380-480 V and
VLT 8502-8652, 525-690 V
Compact IP 00/Chassis, IP 21/NEMA 1
and IP 54/NEMA 12
Cooling Side-by-side
All units in the above-mentioned series require
a minimum space of 225 mm (8.9 in) above the
enclosure and must be installed on a plane floor. This
applies to IP 21/NEMA 1 and IP 54/NEMA 12 units.
Gaining access requires a minimum space of 579
mm (22.8 in) in front of the frequency converter.
All IP 21/NEMA 1 and IP 54/NEMA 12 units in the
above-mentioned series can be installed side by side
without any space between them, since these units
do not require cooling on the sides.