Remote setup selections using digital inputs and the serial communication port. This setup used the
settings from parameter 0-12 This Set-up Linked to. Stop the drive before making changes to open-loop
and closed-loop functions.
Parameter 0-11 Edit Set-up
Table 12: Parameter 0-11 Edit Set-up
Default value: [1] Set-up 1
Change during operation: True
Select the setup to be edited (programmed) during operation, either the active setup or 1 of the inactive setups.
Cannot be edited, but it is useful as a data source to return the other setups to a known state.
[1] Set-up 1 to [4] Set-up 4 can be edited freely during operation, independently of the active setup.
Can also be edited during operation. Edit the selected setup from a range of sources: LCP, FC RS485, FC
USB, or up to 5 fieldbus sites.
AU275636650261en-000101 / 130R033438 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide