Parameter 30-21 High Starting Torque Current [%]
Table 1078: Parameter 30-21 High Starting Torque Current [%]
30-21 High Starting Torque Current [%]
Default value: Size related
Parameter type: Range, 0 - 200.0%
Setup: All setups
Conversion index: -1
Data type: Uint32
Change during operation: True
Set the high starting current that should be applied for the time specified in parameter 30-20 High Starting Torque Time. The in-
creased current will improve the starting torque and starting performance in demanding applications. The high starting torque cur-
rent is valid for VVC+ and flux in speed open loop. The parameter can be used with the following motors:
SPM
IPM
SynRM
PMaSynRM
Parameter 30-22 Locked Rotor Protection
Table 1079: Parameter 30-22 Locked Rotor Protection
30-22 Locked Rotor Protection
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Available for PM motors only, in flux sensorless mode and VVC
+
open-loop mode.
Option
Name
Description
[0]
Off
[1]
On
Protects the motor from the locked rotor condition. The control algorithm detects a possible locked rotor con-
dition in the motor and trips the drive to protect the motor.
Parameter 30-23 Locked Rotor Detection Time [s]
Table 1080: Parameter 30-23 Locked Rotor Detection Time [s]
30-23 Locked Rotor Detection Time [s]
Default value: Size related
Parameter type: Range, 0.05 - 1 s
Setup: All setups
Conversion index: -2
Data type: Uint8
Change during operation: True
Time period for detecting the locked rotor condition. A low parameter value leads to faster detection.
Parameter 30-24 Locked Rotor Detection Speed Error [%]
Table 1081: Parameter 30-24 Locked Rotor Detection Speed Error [%]
30-24 Locked Rotor Detection Speed Error [%]
Default value: 25%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: -1
Data type: Uint32
Change during operation: True
Detects locked rotor condition for SPMSM at high speed.
Light-load detection
Light-load detection is a feature for lift application to ensure lift evacuation in a direction which requires the least energy (UPS ca-
pacity) during an emergency. When a light-load detection and start signal is received, the drive starts in the selected direction. After
the delay in seconds specified in parameter 30-26 Delay Before Measurements, the drive integrates the current consumption within
the time defined in parameter 30-25 Measurement Duration. After completing current integration for 1 direction, the drive starts in
AU275636650261en-000101 / 130R0334580 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals