Use this parameter to configure the drive for either high or normal overload. When selecting the drive size, always review the tech-
nical data in the Operating Guide or the Design Guide to know the available output current.
Allows up to 160% overtorque.
For oversized motor. Allows up to 110% overtorque.
Parameter 1-05 Local Mode Configuration
Table 63: Parameter 1-05 Local Mode Configuration
1-05 Local Mode Configuration
Default value: [2] As mode par. 1-00
Change during operation: True
Select which application configuration mode (parameter 1-00 Configuration Mode), that is application control principle, to use when
a local (LCP) reference is active. A local reference can be active only when parameter 3-13 Reference Site is set to [0] Linked to Hand/
Auto or [2] Local. By default the local reference is active in hand-on mode only.
Allows up to 160% overtorque.
Parameter 1-06 Clockwise Direction
Table 64: Parameter 1-06 Clockwise Direction
Default value: [0] Normal
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
This parameter defines the term clockwise corresponding to the LCP direction arrow. Used for easy change of direction of shaft
rotation without swapping motor wires.
The motor shaft turns in clockwise direction when the drive is connected U⇒U, V⇒V, and W⇒W to the
motor.
The motor shaft turns in counterclockwise direction when the drive is connected U⇒U, V⇒V, and W⇒W
to the motor.