EasyManuals Logo
Home>Danfoss>DC Drives>VLT CANopen MCA 105

Danfoss VLT CANopen MCA 105 Programming Guide

Danfoss VLT CANopen MCA 105
722 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #720 background imageLoading...
Page #720 background image
Powerfactor =
I
1
 × cosϕ1
I
RMS
îš‹ = îš‹
I
1
I
RMS
sincecosϕ1 = 1
The power factor indicates to which extent the drive imposes a load on the
mains supply.
The lower the power factor, the higher the I
RMS
for the same kW perform-
ance.
I
RMS
îš‹ = îš‹ I
1
2
 + I
5
2
 + I
7
2
 + .. + I
n
2
In addition, a high-power factor indicates that the different harmonic cur-
rents are low.
The DC coils in the drive produce a high-power factor, which minimizes the
imposed load on the mains supply.
Preset reference
A defined preset reference to be set from -100% to +100% of the reference
range. Selection of 8 preset references via the digital terminals.
Process PID
The PID control maintains the required speed, pressure, temperature, and
so on, by adjusting the output frequency to match the varying load.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back information on
motor speed. The encoder is used in applications where great accuracy in
speed control is required.
Pulse reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or
33).
R
RCD
Residual-current device.
Ref
MAX
Determines the relationship between the reference input at 100-% full scale
value (typically 10 V, 20 mA) and the resulting reference. The maximum ref-
erence value is set in parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at 0-% value (typi-
cally 0 V, 0 mA, 4 mA) and the resulting reference. The minimum reference
value is set in parameter 3-02 Minimum Reference.
S
SFAVM
Switching pattern called stator flux-oriented asynchronous vector modula-
tion (parameter 14-00 Switching Pattern).
SLC
The SLC (smart logic control) is a sequence of user-defined actions execu-
ted when the associated user-defined events are evaluated as true by the
SLC. (See parameter group 13-** Smart Logic Control).
STW
Status word.
Safe Torque Off (STO)
The STO function brings the drive safely to a no-torque state.
Setup
Save parameter settings in 4 setups. Change between the 4 parameter set-
ups and edit 1 setup, while another setup is active.
Slip compensation
The drive compensates for the motor slip by giving the frequency a supple-
ment that follows the measured motor load keeping the motor speed al-
most constant.
Start-disable command
A start command belonging to Group 2 control commands, see the table
Function Groups under Control Command.
Stop command
A stop command belonging to Group 1 control commands, see the table
Function Groups under Control Command.
AU275636650261en-000101/130R0334720 | Danfoss A/S © 2022.12
Glossary
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals