FC 300 Design Guide
Application Examples
Set t he timer 0 for constant running speed in par. 13-20 [0]. Ex.: 2 sec.
Set t he timer 1 for constant running speed in par. 13-20 [1]. Ex.: 3 sec.
Set Event 0 in par. 1 3-51 [0] to True [1]
SetEvent1inpar. 13-51[1]toOn Reference [4]
Set Event 2 in par. 13-51 [2] to SL Timeout 0 [30]
SetEvent3inpar. 13-51[3]toOn Reference [4]
SetEvent4inpar. 13-51[4]toSL Timeout [30 ]
Set Action 0 in p a r. 13-52 [0] to Select preset ref. 0 [10]
Set A ction 1 in p a r. 13-52 [1] to Start timer 0 [29]
Set Action 2 in p a r. 13-52 [2] to Select preset ref. 1 [11]
Set A ction 3 in p a r. 13-52 [3] to Start timer 1 [30]
Set Action 4 in par. 13-52 [4] to No action [1]
118