EasyManua.ls Logo

Danfoss VLT CDS 803 - Page 42

Danfoss VLT CDS 803
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault
num‐
ber
Alarm/
warning
bit num‐
ber
Fault text Warn‐
ing
Alarm Trip
lock
Cause of problem
80 29 Drive initialised X All parameter settings are initialized to default settings.
87 47 Auto DC Brak-
ing
X The drive is auto DC braking.
95 40 Broken Belt X X Torque is below the torque level set for no load, indicat-
ing a broken belt. See parameter group 22-6* Broken Belt
Detection.
99 Locked rotor X The rotor is locked or the load is too high.
126 Motor Rotating X High back EMF voltage. Stop the rotor of the PM motor.
200 Fire Mode X Fire mode has been activated.
202 Fire Mode Lim-
its Exceeded
X Fire mode has suppressed 1 or more warranty voiding
alarms.
250 New spare part X X The power or switch mode power supply has been ex-
changed. Contact the local Danfoss supplier.
251 New Typecode X X The drive has a new type code. Contact the local Danfoss
supplier.
Troubleshooting
Operating Guide | VLT® Compressor Drive CDS 803
AQ321748767627en-000101 / 130R0570
42 | Danfoss A/S © 2019.12

Other manuals for Danfoss VLT CDS 803

Related product manuals