VLT
®
FCD Series
Shifting from Remote operation to Local operation
in parameter 002 Local/remote operat ion,whilethis
parameter has been set to Remote-operated control
and open loop [1]: The present motor frequency and
direction of rotation will be maintained. If the present
direction of rotation does not respond to the reversing
signal (negative reference), the reference will be set to 0.
Shifting from Local operation to Remote operation
in parameter 002 Local/remote control,while
this parameter has been set to Remote-operated
control and ope n loop [1]: The configuration
selected in parameter 100 Configuration will be
active. The shift will be smooth.
Shifting from Remote control to Local control in
parameter 002 Local/remote operation,whilethis
parameter has been set to Remote-operated control
as parameter 100 [4]: the present reference will
be maintained. If the reference signal is negative,
thelocalreferencewillbesetto0.
Shifting from Local operation to Remote operation
in parameter 002 Local/remote operation, while
this parameter has been set to Remote operation:
The local reference will be replaced by the
remote-operated reference signal.
014 Local stop
(LOCAL STOP)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the local [STOP]-key can be
engaged or disengaged on the control panel
and on the LCP control panel.
Description of choice:
If Not active [0] is selected in this parame
ter,
the [STOP]-key will be inactive.
NB!:
If Not active [0] is selected, the motor cannot
be stopped by means of the [STOP]-key.
015 Local jog
(LOCAL JOGGING)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the jog function on the LCP
control panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter,
the [JOG]-key will be inactive.
016 Local reversing
(LOCAL REVERSING)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select/deselect the reversing
function on the LCP control panel. The key can only
be used if parameter 002 Local/remote operation
is set to Local operation [1] and parameter 013
Localcontrol to Local control, open loop [1] or
Local control as parameter 100 [3].
Description of choice:
If Disable [0] is selected in this parameter, the
[FWD/REV] key will be disabled. See also parameter
200 Output frequency range.
017 Local reset of trip
(LOCAL RESET)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the reset function on the control
panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter,
the reset function will be inactive.
NB!:
Select Not active [0], only if an external reset
signal has been connected via the digital inputs.
018 Lock for data changes
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
36

Table of Contents

Other manuals for Danfoss VLT FCD 311

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 311 and is the answer not in the manual?

Danfoss VLT FCD 311 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 311
CategoryDC Drives
LanguageEnglish

Related product manuals