Instructions
Danfoss inverter compressors 
VZH028-VZH065
© Danfoss | DCS (CC) | 2021.03
8510280P01AA - AN233086441027en-000501 | 1
0
10
20
30
40
50
60
5
15
25
35
45
55
65
75
70
Condensing temperature (°C)
VZH028-044 operating map - R410A (SH 6 K)
-40 -30 -20 -10 0 10 20-35 -25 -15 -5 5 15 25 30 35
Evaporating temperature (°C)
900-6000 rpm
1200-6000 rpm
1800-6000 rpm
2400-6000 rpm
3600-6000 rpm
2400-6000 rpm
Voltage: 400-460V/208-230V
0
10
20
30
40
50
60
5
15
25
35
45
55
65
75
70
Condensing temperature (°C)
VZH052-065 operating map - R410A (SH 6 K)
-30 -20 -10 0 10 20-35 -25 -15 -5 5 15 25 30 35 40
Evaporating temperature (°C)
1000-6600rpm
1800-6600rpm
2400-6000rpm
4200-6000rpm
A:  Model number
B:  Serial Number 
C:  Refrigerant
D:  Manufacturing year
E:  Supply voltage range
F:  Max operating current
G:  Lubricant type and nominal charge
Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering 
practice relating to installation, commissioning, maintenance and service.
 The compressor must only be 
used for its designed purpose(s) 
and within its scope of application 
(refer to «operating limits»). Consult 
Application guidelines and datasheet 
available from cc.danfoss.com
 Never operate 
compressor 
without terminal 
box cover in place 
and secured. 
 Under all circumstances, 
the EN378 (or other applicable 
local safety regulation) 
requirements must be fulfilled. 
Wear protective goggles and 
work gloves.
The compressor must 
be handled with 
caution in the vertical 
position (maximum 
offset from the 
vertical : 15°).
The compressor is delivered under 
nitrogen gas pressure (between 
0.3 and 0.4 bar / 4 and 6 psi). Do 
not disassemble bolts, plugs, 
fittings, etc... unless all pressure 
has been relieved from the 
compressor.
Operating limits
Quick connect 
spade terminals 
VZH028-044
push
push
push
Electrical connections
All the above limits, temperatures and speeds, are secured by parameters in the drive and 
application controller softwares.
VZH028 - VZH065 compressors can be 
powered by the dedicated variable speed 
drive or third party drive.
When Danfoss drive is selected, check carefully 
for compatibility between compressor model 
and variable speed drive.
Compressor 
model
Driver 
power
Driver 
model
VZH028-J/G 6kW CDS803
VZH035-J/G 7.5kW CDS803
VZH044-J/G 10kW CDS803
VZH028-H 7.5kW CDS303
VZH035-H 11kW CDS303
VZH044-H 11kW CDS303
VZH052-J 11kW CDS303
VZH065-J 11kW CDS303
VZH052-G 11kW CDS303
VZH065-G 15kW CDS303
VZH052-H 15kW CDS303
VZH065-H 22kW CDS303
Note :  These instructions replace instructions 
in grommet kit. 
VZH028-044
VZH052-065
Ring connect screw terminals
C & Q terminal box type
VZH052-065
VZH67F Map
Solid line bondaries:
SH=6K
Dash line bondaries:
need ensure Tdis 
<135°C