EasyManuals Logo

Dantherm CDP 50 User Manual

Dantherm CDP 50
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
EN
Important! If the dehumidier is not functioning correctly, shut it down immediately!
Fault nding
Use this table to localize and solve a possible problem or fault:
Fault Possible cause Solution
The dehumidier
does not work
• no light in the LEDs
on the display
- • Check the external
fuses
• Check the power
supply to the unit
The compressor does not
work
• the display shows wrong
type
The compressor has stopped
automatically caused by a
too high temperature on the
condenser
If the unit does not start again
after 45 minutes, check the
following:
• Check that the fan(s) is
running
• Check if the lter in the duct
kit is dirty, clean if necessary.
• Check if the condenser coil
is dirty
• Check if the room tempera-
ture is higher than 36 °C. If the
room temperature is higher
than 36 °C, the unit must be
stopped
• Check that the duct
openings are not covered
The dehumidier does not
work
Check the built-in or the exter-
nal hygrostat, if any, by setting
it to a low relative humidity,
e.g. 10 – 20 %RH.
If the unit still does not start,
check the built-in or external
hygrostat for defects.
More help
If you cannot nd the reason for the fault, switch o the unit immediately in order to prevent
further damage.
Contact a service technician or a Dantherm representative.
Fault nding guide

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dantherm CDP 50 and is the answer not in the manual?

Dantherm CDP 50 Specifications

General IconGeneral
BrandDantherm
ModelCDP 50
CategoryDehumidifier
LanguageEnglish

Related product manuals