RS-485 Interface
Continued
Register Byte
Database
parameter
Min Max
De-
fault
Description
7
12
Evap_
temp2
(decimal)
-40 100 0
Temperature from evaporator 2:
Usage the same as above.
13
Evap_
temp2
(fraction)
-40 100 0
8
14
Cond_
temp1
(decimal)
-40 100 0
Temperature from condenser:
Usage the same as above.
15
Cond_
temp1
(fraction)
-40 100 0
9
16
Aux_temp
(decimal)
-40 100 0
Temperature from auxiliary sensor:
Usage the same as above.
17
Aux_temp
(fraction)
-40 100 0
10
18
Amb_temp
(decimal)
-40 100 0
Temperature of ambient air:
Usage the same as above.
19
Amb_temp
(fraction)
-40 100 0
11
20
Amb_hum
(High byte)
0 100 0
Humidity of ambient air:
High byte has no meaning and always contains zero.
Only low byte can be used.
21
12
22 RH_set 40 95 40 Setpoint value of desired humidity.
23 RH_Fan 40 95 40 Setpoint value of humidity for exhaust fan start.
13
24
Temp_set
(decimal)
0 36 0
Setpoint value of desired temperature:
Usage the same as for Evap_temp1.
25
Temp_set
(fraction)
16
30 Fail_start 0 1 0 State of Fail_start mode
31 SB_mode 0 1 0 Stand-by mode state
17
32 DEH_mode 0 1 0 Dehumidifying state
33 Ice_mode 0 1 0 Deicing state