Register Byte
Database
parameter
Min Max
De-
fault
Description
18
34 LP_mode 0 1 0 LP fail mode state
35 Sens_mode 0 1 0 Sensor fail mode state
19
36 HP_mode 0 1 0 HP fail mode state
37 Amb_mode 0 1 0 Ambient fail mode state
20
38
AmbT_
mode
0 1 0 Ambient temperature fail mode state
39
AmbRH_
mode
0 1 0 Ambient humidity fail mode state
21
40
SW Build
number
(high)
0
65535 x SW build number
41
SW Build
number(low)
0
22
42
SW Version
(Major)
0 255 x SW version major
43
SW Version
(Minor)
0 255 x SW version minor
23
44
HP Alarm
Temp.
(Decimal)
0 99 60
HP fail occurs when Cond_temp1 is more then this
value.
Usage the same as for Evap_temp1.
45
HP Alarm
Temp.
(Fraction)
41
80
Fan_func-
tion
0 1 0 Enable FAN function in standby mode
81
42
82
Time_wait_
fan
60 7200 3600
Time to wait until FAN will be started in standby
mode, if enabled (seconds)
83
43
84
Time_run_
fan
15 600 60
Time to run FAN in standby mode if enabled (sec-
onds)
85
44
86 RH_Fen 0 1 0 Enable/disable Exhaust Fan function
87
Service_ena
0 1 0 Enable/disable Service interval function
45
88
Service_int 0 99 0 Service interval value in weeks
89
RS-485 Interface
Continued