24
The entered month and day are the START DATE of the special day.
Press the Enter key. The cursor will ash on the SETTING input. Press the Up or Down keys to
scroll through the choices – there are two: PRIMARY and SECONDARY.
Press ESC key to go back to the main menu. Press ESC key one more time to go back to normal
operation mode.
Once selections have been made and with the cursor ashing in the title block, press the Down
key to see the next screen. The following message will be displayed (entries are for reference
only):
The alarm may be set to either yes or no. Press the Enter key to move the cursor from one alarm
to the next. Press the Up or Down key to change from Y (yes) to N (no).
Once selections have been made and with the cursor ashing in the title block, press the Down
key to see the next screen. The following message will be displayed (entries are for reference
only):
The alarm may be set to either yes or no. Press the Enter key to move the cursor from one alarm
to the next. Press the Up or Down key to change from Y (yes) to N (no).
Once selections have been made and with the cursor ashing in the title block, press the Down
key to see the next screen. The following message will be displayed (entries are for reference
only):
Zone Alarm Function 1
Stby Off
CW Sensor Y N
DA Sensor Y N
Fan Overload Y N
Smoke Detect Y N
Condensation N N
Fire Status N Y
Zone Alarm Function 2
Stby Off
C1 hi Press Y N
C1 Lo Press Y N
C2 Hi Press Y N
C2 Lo Press Y Y
Short Cycle N N
Maint Timer N Y
Zone Alarm Function 3
Stby Off
Hi Humidity Y N
Low Humidity Y N
Humidifier Y N
DA Low Temp Y Y
RA Low Temp N N
RA Hi Temp N Y