EasyManua.ls Logo

Data Aire dara-4g2 - Wiring Connections; Wiring Terminal Connections

Data Aire dara-4g2
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14•dara-4g
2
User Manual
4. WIRING CONNECTION
IMPORTANT NOTE:
• Thewiringbetweendara-4g
2
and units must be at least 18 AWG wires and met the local
electrical code.
• Thepowersupplydoesnotcomewithdara-4g
2
panel. Power supply must be provided by
customer. See dara-4g
2
specicationsbelowforpowerinputrequirement.
Wiring Terminal Connections
TB1
Power
TB1-1 24 VAC Power hot
TB1-2 24 VAC Common
TB1-3 Earth Ground
Alarm Signal Relay
TB1-4 Alarm Relay Normally open (Connect to BAS or monitoring panel)
TB1-5 Alarm Relay Common (Connect to BAS or monitoring panel)
TB1-6 Alarm Relay Normally closed (Connect to BAS or monitoring panel)
To HVAC Unit 1
TB1-7 Relay Common (To remote shutdown connection of HVAC unit 1)
TB1-8 Relay Normally Open (To remote shutdown connection of HVAC unit 1)
TB1-15 Alarm Input (To HVAC unit alarm relay common)
TB1-16 Alarm Input (To HVAC unit alarm relay normally open)
To HVAC Unit 2
TB1-9 Relay Common (To remote shutdown connection of HVAC unit 2)
TB1-10 Relay Normally Open (To remote shutdown connection of HVAC unit 2)
TB1-17 Alarm Input (To HVAC unit alarm relay common)
TB1-18 Alarm Input (To HVAC unit alarm relay normally open)
To HVAC Unit 3
TB1-11 Relay Common (To remote shutdown connection of HVAC unit 3)
TB1-12 Relay Normally Open (To remote shutdown connection of HVAC unit 3)
TB1-19 Alarm Input (To HVAC unit Alarm relay common)
TB1-20 Alarm Input (To HVAC unit Alarm relay normally open)
To HVAC Unit 4
TB1-13 Relay Common (To remote shutdown connection of HVAC unit 4)
TB1-14 Relay Normally Open (To remote shutdown connection of HVAC unit 4)
TB1-21 Alarm Input (To HVAC unit alarm relay common)
TB1-22 Alarm Input (To HVAC unit alarm relay normally open)
Optional Zone Temperature and humidity sensor
TB1-23 NTC Temperature sensor
TB1-24 NTC Temperature sensor
TB1-25 Humidity sensor signal output (OUTH)
TB1-26 Humidity sensor power GND (M)
TB1-27 Humidity sensor power G+