2.7.6 Connection Sizes, Air Cooled Units
Model Number
Liquid Line
(2 per unit)
Hot Gas Line
(2 per unit)
Suction Line
(2 per unit)
GFA* 021
1/2” (12 mm) O.D.
1/2” (12 mm) O.D.
7/8” (22 mm) O.D.
GFA* 028
1/2” (12 mm) O.D.
5/8” (16 mm) O.D.
7/8” (22 mm) O.D.
GFA* 035
1/2” (12 mm) O.D.
5/8” (16 mm) O.D.
1-1/8” (29 mm) O.D.
GFA* 046
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
1-1/8” (29 mm) O.D.
GFA* 056
5/8” (16 mm) O.D.
3/4” (19 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 070
5/8” (16 mm) O.D.
3/4” (19 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 091
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 106
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
1-3/8” (35 mm) O.D.
* D=Downow U=Upow
NOTE: Units will have a liquid line and either a hot gas (condenser) or suction line (condensing unit).
Note: Field connections at the indoor evaporator and remote condenser or condensing
unit will not necessarily be the same as the eld pipe size required. In some cases
these will vary signicantly.
2.7.7 Field Piping, Remote Condenser/Condensing Unit Above Evaporator