2.7.6 Connection Sizes, Air Cooled Units
Model Number
Liquid Line
(2 per unit)
Hot Gas Line
(2 per unit)
Suction Line
(2 per unit)
GFA* 021
1/2” (12 mm) O.D.
1/2” (12 mm) O.D.
7/8” (22 mm) O.D.
GFA* 028
1/2” (12 mm) O.D.
5/8” (16 mm) O.D.
7/8” (22 mm) O.D.
GFA* 035
1/2” (12 mm) O.D.
5/8” (16 mm) O.D.
1-1/8” (29 mm) O.D.
GFA* 046
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
1-1/8” (29 mm) O.D.
GFA* 056
5/8” (16 mm) O.D.
3/4” (19 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 070
5/8” (16 mm) O.D.
3/4” (19 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 091
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
1-3/8” (35 mm) O.D.
GFA* 106
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
1-3/8” (35 mm) O.D.
* D=Downow U=Upow
NOTE: Units will have a liquid line and either a hot gas (condenser) or suction line (condensing unit).
Note: Field connections at the indoor evaporator and remote condenser or condensing
unit will not necessarily be the same as the eld pipe size required. In some cases
these will vary signicantly.
2.7.7 Field Piping, Remote Condenser/Condensing Unit Above Evaporator