39
7.3.4 How to Manually Open and Close an (EEV)
This can be done in the Regulation Menu as shown below
Step 1: Follow previous screens to the Regulation Menu screen below
Step 2: Change “Enable manual valve position” from 0 to 1 and “Manual valve position from 0stp to a
desired step value. There are 480 steps total for the EEV. If you would like the valve to open 62.5%,
enter “300stp” such as below: