47
MAINTENANCE/INSPECTION CHECKLIST
Reheat (Quarterly)
___ Inspect element (and clean if required)
___ Check wire connections
___ Check high limit switch operation
___ Record amps #1 ____ A #2 ____ A #3 _____ A
Humidier (Steam Generator) is equipped
___ Inspect drain valve/trap/drain line for deposits
___ Check for leaks (make-up water/hoses)
___ Check humidier canister for deposits and water level (replace if needed)
___ Check operation
___ Check condition of steam hoses and clamps
___ Record humidier amp draw L1____ L2 ____ L3 ____
Air Cooled Condenser (if applicable)
___ Inspect coil/clean if required
___ Inspect motor/motor mounts
___ Inspect fan blade(s)
___ Check wire connections
___ Inspect piping for leaks
___ Heated receiver sight-glass #1 ___ #2 ____
Dry Cooler (if applicable)
___ Inspect coil/clean if required
___ Inspect motor/motor mounts
___ Inspect fan blade(s)
___ Check wiring
___ Inspect piping for leaks
___ Check glycol solution ____ %