Superheat and Suction Pressure
Trouble Shooting Guide
Low Suction Pressure and High Superheat
1. Moisture, dirt, wax
2. Undersized valve*
3. High superheat adjustment
4. Gas charge condensation
5. Dead thermostatic element charge
6. Wrong thermostatic charge
7. Evaporator pressure drop - no external equalizer
8. External equalizer location
9. Restricted or capped external equalizer
10. Low refrigerant charge
11. Liquid line vapor
a. Vertical lift
b. High friction loss
c. Long or small line
d. Plugged drier or strainer
12. Low pressure drop across valve
a. Same as #11 above
b. Undersized distributor nozzle or circuits
c. Low condensing temperature
High Suction Pressure - Low Superheat
1. Oversized valve*
2. TEV seat leak
3. Low superheat adjustment
4. Bulb installation
a. Poor thermal contact
b. Warm location
5. Wrong thermostatic charge
6. Bad compressor - low capacity
7. Moisture, dirt, wax
8. Incorrectly located external equalizer
Low Suction Pressure - Low Superheat
1. Low load
a. Not enough air
b. Dirty air lters
c. Coil icing
2. Poor air distribution
3. Poor refrigerant distribution
4. Improper compressor-evaporator balance
5. Evaporator oil logged
6. Flow from one TEV affecting another’s bulb
* Data Aire has ensured that valves are size properly as the unit ships from the factory.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire MINI CEILING SERIES and is the answer not in the manual?

Data Aire MINI CEILING SERIES Specifications

General IconGeneral
BrandData Aire
ModelMINI CEILING SERIES
CategoryChiller
LanguageEnglish

Related product manuals