DKG-309 User Manual
(11.05.2009)
6.10
This led is designed to help the periodic maintenance of the genset to be made consistently.
The periodic maintenance is basically carried out after a given engine hours (for example 200
hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for
example 12 months).
operation.
The unit has both programmable engine hours and maintenance time limit. The engine hours is
programmable with 50-
hour steps, the time limit is programmable with 1
programmed values is zero, this means that the parameter will not be used. For example a maintenance
period of 0 months
be no time limit. If the en
gine hours is also selected as 0 hours this will mean that the SERVICE
REQUEST display will be inoperative.
When the engine hours
flash and the service request relay function will be a
The service request relay function may be assigned to spare relays using
program parameters. Also relays on an extension module may be assigned to this function.
period,
press together the ALARM MUTE and LAMP TEST keys
The remaining engine hours and the remaining time limit are kept stored in a non
and are not affected from
The time and engine hours to service
6.11
The unit features a non-
erasable incremental engine hour meter. The hour meter information is
kept in a non-
volatile memory and is not
The engine hours may be displayed
This led is designed to help the periodic maintenance of the genset to be made consistently.
The periodic maintenance is basically carried out after a given engine hours (for example 200
hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for
has no effect on the genset
The unit has both programmable engine hours and maintenance time limit. The engine hours is
hour steps, the time limit is programmable with 1
programmed values is zero, this means that the parameter will not be used. For example a maintenance
unit
will request maintenance only based on engine hours
gine hours is also selected as 0 hours this will mean that the SERVICE
REQUEST display will be inoperative.
the time limit is over, the
flash and the service request relay function will be a
ctive.
The service request relay function may be assigned to spare relays using
program parameters. Also relays on an extension module may be assigned to this function.
SERVICE REQUEST
led, and reset the service
press together the ALARM MUTE and LAMP TEST keys
The remaining engine hours and the remaining time limit are kept stored in a non
The time and engine hours to service
are displayed in the
erasable incremental engine hour meter. The hour meter information is
volatile memory and is not
affected from power supply failures.
The engine hours may be displayed
STATISTICAL COUNTERS menu.
V-02
- 18 -
This led is designed to help the periodic maintenance of the genset to be made consistently.
The periodic maintenance is basically carried out after a given engine hours (for example 200
hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for
has no effect on the genset
The unit has both programmable engine hours and maintenance time limit. The engine hours is
steps. If any of the
programmed values is zero, this means that the parameter will not be used. For example a maintenance
will request maintenance only based on engine hours
, there will
gine hours is also selected as 0 hours this will mean that the SERVICE
led (red) will start to
The service request relay function may be assigned to spare relays using
Relay Definition
program parameters. Also relays on an extension module may be assigned to this function.
led, and reset the service
press together the ALARM MUTE and LAMP TEST keys
The remaining engine hours and the remaining time limit are kept stored in a non
-volatile memory
menu.
erasable incremental engine hour meter. The hour meter information is