DPR-145 User Manual V-3.0 (14.09.2016)
-17-
12 parameters are available in total. Parameter values may be modified with Function 10
(Write Multiple Registers). All values should be sent at once.
ADDRESS
NAME
DESCRIPTION
LENGTH
R/W
TYPE
X
0
Alarm 1
Channel 1 Alarm temperature (°C)
16 BIT
R/W
unsigned
word
1
1
Alarm 2
Channel 2 Alarm temperature (°C)
16 BIT
R/W
unsigned
word
1
2
Alarm 3
Channel 3 Alarm temperature (°C)
16 BIT
R/W
unsigned
word
1
3
Alarm 4
Channel 4 Alarm temperature (°C)
16 BIT
R/W
unsigned
word
1
4
Trip 1
Channel 1 Trip temperature (°C)
16 BIT
R/W
unsigned
word
1
5
Trip 2
Channel 2 Trip temperature (°C)
16 BIT
R/W
unsigned
word
1
6
Trip 3
Channel 3 Trip temperature (°C)
16 BIT
R/W
unsigned
word
1
7
Trip 4
Channel 4 Trip temperature (°C)
16 BIT
R/W
unsigned
word
1
8
Fan
Channel
Fan relay channel selection
16 BIT
R/W
unsigned
word
1
9
Fan ON
Fan Turn On Temperature (°C)
16 BIT
R/W
unsigned
word
1
10
Fan OFF
Fan Turn Off Temperature (°C)
16 BIT
R/W
unsigned
word
1
11
Cable
Lenght
Cable Length (m)
16 BIT
R/W
unsigned
word
1
12
Cable
Section
Cable Section(mm
2
)
16 BIT
R/W
unsigned
word
0.01
13
Channel_1
Alarm
Alarm enable parameter of the
related channel
16 BIT
R/W
unsigned
word
1
14
Channel_2
Alarm
Alarm enable parameter of the
related channel
16 BIT
R/W
unsigned
word
1
15
Channel_3
Alarm
Alarm enable parameter of the
related channel
16 BIT
R/W
unsigned
word
1
16
Channel_4
Alarm
Alarm enable parameter of the
related channel
16 BIT
R/W
unsigned
word
1
17
Baud Rate
RS-485 data rate
16 BIT
R/W
unsigned
word
1
18
Modbus
Address
Modbus address of the device
16 BIT
R/W
unsigned
word
1
6.2 PROGRAM PARAMETERS