DPR-145 User Manual V-3.0 (14.09.2016)
-8-
SELECTED CHANNEL LEDS: indicates
the related channel to alarm or
information on display.
MOD LEDS: indicated the current mode
of operation.
ALARM LEDS: indicates the type of
alarm if any.
TEST LED: turns on during lamp test or
relay test.
PPROGRAM LED: turns on in program
mode.
The unit has 4 operating modes: SCAN, AUTO, MAN, MAX.
Every depression of the MODE button switches the unit to the next operating mode.
Related mode led will turn on. Channel leds on the right side (1,2,3,4) indicate the
related channel number.
• SCAN: Displays channel temperatures, switches to the next channel every 5
seconds.
• AUTO: Displays the temperature of the highest channel.
• MAN: Displays the temperature of the selected channel. Channels may be
scrolled with and pushbuttons.
• MAX: Displays the maximum recorded temperature of the selected channel.
Channels may be scrolled with and pushbuttons.
NOTE: If any of or pushbuttons is depressed in SCAN or AUTO modes, then
the unit will automatically switch to the MANUAL mode. If no pushbutton is depressed
during 30 minutes, it will resume previous mode.