V110120E iBoot-G2+ Page 23
A
ction:
C
ycle
Outlet:Exp2
Ok
iBoot>
set autoping <1a | 1b | 2 | 3> ipaddress
<dotted decimal>
This command is used to set the IP address of
AutoPing 1 or AutoPing 2
0.0.0.0
set autoping <1a | 1b | 2 | 3> frequency
<1-999>
This command is used to set the frequency, in
seconds (how often the iBoot-G2+ sends the ping) for
each of the AutoPings.
10
set autoping <1a | 1b | 2 | 3> failcount <1-
999>
This command is used to set the number of
consecutive failures the AutoPings must detect before
the AutoPing considers the pinged device to be failed.
3
set autoping 1 logic <a | and | or>
Sets logic for AutoPing 1. A = A Only, and = A and B,
or = A or B.
A and B
set autoping <1 | 2 | 3> action <none | on-
latch | on-follow | off-latch | off-follow |
cycle | cycle-once>
This command is used to set the action that the iBoot-
G2+ will perform when the AutoPing triggers.
None
Heartbeat Commands
These commands are only available to the administrator.
get heartbeat This command displays the heartbeat settings
Source:USBStatusTriggerCount
Frequency:10OK0
FailCount:3
Action:CycleOnce
Outlet:Main
set heartbeat source <none | usb |
network>
This command sets the source for the heartbeat.
Either USB or Network
None
set heartbeat frequency <1-999> This command is used to set the frequency, in
seconds. How often the iBoot-G2+ expects the
heartbeat
10
set heartbeat failcount <1-999>
This command is used to set the number of
consecutive failures the heartbeat must detect before
the iBoot-G2+ considers the device to be failed.
3
set heartbeat action <none | on-latch | on-
follow | off-latch | off-follow | cycle | cycle-
once>
This command is used to set the action that the iBoot-
G2+ will perform when the heartbeat detector triggers.
None
Set heartbeat outlet <main | exp1 | exp2> This command sets the outlet that the heartbeat will
trigger.
Main
User Commands
These commands are only available to the administrator.
set password <user | admin> <old> <new>
<repeat>
This command is used to set the password of either
the user or administrator.
user
admin
Event Commands
These commands are only available to the
administrator.
get events
This command displays all scheduled events as shown
below. Example:

Other manuals for Dataprobe iBoot G2+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dataprobe iBoot G2+ and is the answer not in the manual?

Dataprobe iBoot G2+ Specifications

General IconGeneral
BrandDataprobe
ModeliBoot G2+
CategorySwitch
LanguageEnglish

Related product manuals