16
On systems with the UV monitor, the system will display the same screens as on the
Microlene5.1 except the UV Intensity replaces the home screen. The UV Intensity
screen displays the level of UV light detected by the sensor. UV intensity can be
affected by poor water quality, scaling on the quartz sleeve and/or sensor, lamp
failure or lamp expiring. The following screens show the UV Intensity dropping.
Below 56%, the numbers and warning sign turn red and an audible chirp is given
by the ballast every 15 seconds. Below 51%, the screen is solid red and a constant
audible alarm is given. This alternates with a screen indicating “water may be unsafe
forconsumption”.Withthesolenoidmodule,thecontrollerde-activatesthesolenoid
valve,shuttingoffallwaterow.
audible chirp every
15 seconds
audible chirp every
15 seconds
constant audible
alarm
cycles with red low
uv screen
Lamp Countdown Sequence
The system counts down the number of days until a lamp change is required.
MCXS System
MCS System
At thirty days remaining, the LED or display screen will change to a yellow caution
indicator. At seven days remaining, the sytem will additionaly repeat an audible chirp.
Past the zero day threshold, the LED or display screen changes to solid red with a
continuous buzzer.
MCXS System