325.6610.17 - 12 -
Max. Distance Receiver to
Sensor/Transmitter: 1000 ft.
Wires (Xmttr/Receiver) 2
Sample Draw None
Sensor Check Optional
Housing
Sensor/Transmitter:
Dimensions: 3.2 in.(W) x 11.0 in.(H)* x 2.2 in.(D)
*12.6 in.(H) with gas-generator
Weight: 1 lb.
Materials: Electronic Housing Tube-PVC
Junction Box-polycarbonate
Receiver:
Dimensions: 10.9 in.(W) x 8.6 in.(H) x 5.3 in.(D)
Weight: 5 lb.
Materials: Enclosure-polystyrene
Clear Front-polycarbonate
Battery:
Dimensions: 10.5 in.(W) x 9.0 in.(H) x 6.5 in.(D)
Weight: 15 lb.
Mounting: Wall
ENCLOSURES: NEMA 4X(IP65)
OPTIONS:
4 ANO Option Contains circuitry for transmitting four 0-20 mA or 4-20 mA analog
current outputs proportional to gas concentration levels. The analog
outputs are not isolated since they all share the same “circuit
common” return point (Refer to Figure 2-4).
6 DO Option Contains six additional SPST relay circuits, thus allowing for two
relays for each gas channel.
Communications Plug-in models for RS232 or RS485
ACCESSORIES:
External Battery Includes battery (w/storage case) allowing a minimum of 24 hours
of operation
Sensor Cable Available in any length (in feet) up to 1000 ft. max.
Sensor-Check Generators Attach to end of sensor. Discharge gas into the sensor to verify
sensor and receiver operation. Controlled by the Receiver.
SENSOR:
Sensor Type Electrochemical (EC)
Minimum Detectable Chlorine: 0.1 ppm
Concentration Sulfur Dioxide: 0.1 ppm
Calibration Mode automatic, remote single person, non-intrusive