24V
OPERATING PARAMETERS
Collectivity function: if it is activated it deactivates both opening and closing inputs for the whole duration of automatic opening
and closing
• 000: disabled
• 001: activated only upon opening
• 002: activated on automatic opening and closing
Unused parameter
“Reversal” mode selection (during the manoeuvre a command impulse reverse the mouvement) or “step by step” (during the
manoeuvre a command impulse stops the mouvement). A next impulse restart the operator to the opposite direction.
• 000: “reversal function”
• 001: “step by step function”
PHOTO 1
PHOTO input functioning: If=0: photocell enabled while closing and starting when the gate is stopped; if=1
photocells are always enabled; if=2 photocells are enabled while closing only. When enabled, its activation
provokes: the inversion (while closing), the stop (while opening) and prevent the starting (when gate is closed).
If=3-4-5, the operation is the same as the values 0-1-2 but with “close immediately” enabled: in any case, during
the opening and/or the pause time, removal of a possible obstacle causes the gate automatically closes after a
! xed delay of 2 sec.
• 000: photocell enabled while closing and when gate is stopped
• 001: photocells always enabled
• 002: photocells enabled only while closing
• 003: as 000 but with “close immediately” enabled
• 004: as 001 but with “close immediately” enabled
• 005: as 002 but with “close immediately” enabled
PHOTO 2
Operation mode selection of the warning light output:
If> 1 “courtesy light” (output ON during each movement, OFF when the motor stops, after the setting delay)
• >001 : “courtesy light” off delay
(2sec………………255sec)
Unused parameter
“soft start” function: motors accelerate gradually until they reach the set speed, avoiding sudden departures
• 000: “soft start” deactivated
• 001: “soft start” activated
Adjust the inversion on obstacle period (detected by internal anti-crushing sensor or by the safety input when activated): If = 0
it makes a complete inversion, if> 0 indicates the duration (in seconds) of the run, after inversion resulting from detection of an
obstacle during the opening.
• 000: complete reversal on obstacle
• >000: duration of reversal on obstacle
(1sec……………..10sec)
Adjust the inversion on obstacle period (detected by internal anti-crushing sensor or by the safety input when activated): If = 0
it makes a complete inversion, if> 0 indicates the duration (in seconds) of the run, after inversion resulting from detection of an
obstacle during the closing.
• 000: complete reversal on obstacle
• >000: duration of reversal on obstacle
(1sec……………..10sec)
Facilitation manual release: If"0, after detecting the locking stop, the engine reverses for a brief time to release the pressure on
it, and thus facilitate the manual release. The set value shows the length of the inversion. If=0 function disabled
• 000: facilitating release disabled
• >000: facilitation activated with release time equal to:
(1x25ms……5x25ms)
Secondary closing force adjustment: it adjusts the duration of the last part of the stroke during which the value of the force is
managed separately by P060. The set value indicates the number of rotor’s revolutions.
(20...................................255)
Adjustment of the closing stroke margin: it adjusts the duration of the last part of the stroke during which an obstacle is seen as
a mechanical stop, blocking the motor without performing the reversal. The set value indicates the number of rotor’s revolutions.
(15...................................255)
Adjustment of secondary closing force: adjusts the motor’s force during the last part of the closing stroke de! ned by P058. (2...................................100)
“Energy saving” mode: If=1 after 10sec of inactivity, the control panel turns the 24V outputs and the display off that will be turned
on at ! rst command received (use recommended battery-powered and / or solar panel).
• 000: “Energy saving” not active
• 001: “Energy saving” active
OUTPUT_2 functioning selection:
If=0 “boost” output for electric lock power supply art. 110; If=1 ! xed # ashing output (for # ashing lights with internal intermittent
circuit); If=2 intermittent # ashing output; If=3 Fixed open gate LED” (output always On when the gate is open, OFF at the end of
a closure manoeuvre); If=4 Intermittent open gate LED” (slow intermittent output during opening and fast during closing, always
ON with gate open, always OFF only at the end of a closing manoeuvre); If=5 Courtesy light” (output ON during every movement,
OFF when the motor stops, after the delay set); If=6 24V output for electric lock in ! xed mode; If=7 24V output for electric lock in
inverted mode; If=8 output for accessories power supply; If=9 24V commanded by ELOCK_IN input in impulse mode; If=10 24V
output commanded by ELOCK_IN input in bistable mode; If>10 24V output commanded by ELOCK_IN input in timed mode (the
value set indicates the switch-off delay in seconds).
Warning: If P062=8, output functioning is determined by the functioning envisioned in parameters P061 (Energy Saving) and
P071 (Safety devices autotest).
• 000: “boost” output for electric lock power supply art. 110
• 001: “! xed # ashing output
• 002: “intermittent # ashing output
• 003: “Fixed open gate LED
• 004: “Intermittent open gate LED
• 005: “Courtesy light (switching off delay set from P052)
• 006: “24V