If the alarm button is illuminated, press it
to see the current alarm(s).
Press
↓↓
repeatedly to see all current alarms
1
.
Where phase-sequence reversal is indicated, a qualified person should interchange any two branch-circuit wires.
Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owner’s Manual
T.A.B. Enable Blower(s)
Data subject to change without notice.
188
1. For an explanation of an alarm, press Prg while the alarm message is being displayed.
For a list of alarm messages, see Operation - Alarm Messages.
DECTRON
VOLTAGE FAILURE
If the alarm VOLTAGE FAILURE appears, then the unit is equipped with a
voltage monitor, which prevents operation in the event of over-voltage, under-
voltage, phase loss, or phase-sequence reversal. (See following pages.)
In this case, a person qualified to work with exposed line-voltage electric terminals
should determine which failure condition is present, and correct as necessary.
Continuous operation with voltages greater than 110% of nameplate voltage or less
than 90% of nameplate voltage may damage motorized equipment. Where this is the
case, consult an electrician for corrective measures.
Operation with a missing phase may damage motorized three-phase equipment.
Correct any missing phase.
Phase-sequence reversal will cause three-phase motors to turn backward.
If the supply blower fails to run, check the controller interface.
ALARM MESSAGES
SCROLL DOWN
TO VIEW
--- ALARM ---
XXXXXXXX
--- ALARM ---
XXXXXXXX
--- ALARM ---
XXXXXXXX
NOTICE
Risk of unit damage.
Do not alter any factory-installed wires.
WARNING
Risk of electric shock. Can cause injury or death.
Exposed electric terminals may be present inside
electrical and control enclosures.
Only
persons qualified to work with exposed line-
voltage terminals should be allowed to open the unit
electrical enclosure.
Follow all safety regulations.
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect, lock, and tag all sources of electric energy before disconnecting any wires.
T.A.B.
↓↓
↓↓