Installer level - #SECONDARY INSTAL.P Menu
Parameter Adjustment range Description Factory
setting
Customer
setting
BUILD.INERTIA
(1)
0 (10 hours) to 10
(50 hours)
Characterisation of building’s inertia:
0 for a building with low thermal inertia.
3 for a building with normal thermal
inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
3 (22 hours)
CIRC.CURVE A
(2)
0 to 4 Heating curve of the circuit A
¼ "CIRC.CURVE ..", page 58
1.5
ANTICIP.A
(1)
0.0 to 10.0 Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 58
NO
ROOM INFL.A
(1)
0 to 10 Influence of room sensor A
¼ "ROOM S.INFL", page 59
3
CIRC.CURVE B
(2)
0 to 4 Heating curve of the circuit B
¼ "CIRC.CURVE ..", page 58
0.7
ANTICIP.B
(1)
0.0 to 10.0 Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 58
NO
ROOM INFL.B
(1)
0 to 10 Influence of room sensor B
¼ "ROOM S.INFL", page 59
3
CIRC.CURVE C
(2)
0 to 4 Heating curve of the circuit C
¼ "CIRC.CURVE ..", page 58
0.7
ANTICIP.C
(1)
0.0 to 10.0 Activation and adjustment of the
anticipation time
¼ "ANTICIP.A, ANTICIP.B,
ANTICIP.C ", page 58
NO
ROOM INFL.C
(1)
0 to 10 Influence of room sensor C
¼ "ROOM S.INFL", page 59
3
SCREED DRYING NO, B, C, B+C
Drying the floor
¼ "SCREED DRYING", page 58
NO
START DRYING TEMP
(3)
20 to 50 °C Screed drying start temperature 20 °C
STOP DRYING TEMP
(3)
20 to 50 °C Screed drying stop temperature 20 °C
NB DAYS DRYING
(3)
0 to 99
0
NIGHT
(1)
DEC.
The lower temperature is maintained
(Night mode)
¼ "NIGHT", page 59
DEC.
STOP
The boiler is stopped (Night mode)
¼ "NIGHT", page 59
IN 0-10V
OFF /
TEMPERATURE /
POWER %
Activating the 0-10 V function
¼ "Function 0-10 V", page 60
OFF
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f
(3) The parameter is only displayed if SCREED DRYING is different from OFF
(4) The parameter is only displayed if IN 0-10V is set to ON.
(5) The parameter is only displayed if P.DHW is set to PUMP
(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
(7) The parameter is only displayed if LEG PROTEC is different from OFF
5. Commissioning Diematic iSystem For C 330 / C 630 ECO