4.1.5 Status line texts
Status text Condition Comment
BLOCK Block mode is activated
SIMPLE TEST Test mode is activated
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min Test mode is activated and test timer counting down
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN Genset stopped or running and no other action tak-
ing place
ISLAND SEMI
READY ISLAND AUTO Genset stopped in Auto
ISLAND ACTIVE Genset running in Auto
AMF MAN Genset stopped or running and no other action tak-
ing place
AMF SEMI
READY AMF AUTO Genset stopped in Auto
AMF ACTIVE Genset running in Auto
FIXED POWER MAN Genset stopped or running and no other action tak-
ing place.
FIXED POWER SEMI
READY FIXED P AUTO Genset stopped in Auto
FIXED POWER ACTIVE Genset running in Auto
PEAK SHAVING MAN Genset stopped or running and no other action tak-
ing place.
PEAK SHAVING SEMI
READY PEAK SHAV AU-
TO
Genset stopped in Auto
PEAK SHAVING ACTIVE Genset running in Auto
LOAD TAKEOVER MAN Genset stopped or running and no other action tak-
ing place
LOAD TAKEOVER SEMI
READY LTO AUTO Genset stopped in Auto
LTO ACTIVE Genset running in Auto
MAINS P EXPORT MAN Genset stopped or running and no other action tak-
ing place
MAINS P EXPORT SEMI
READY MPE AUTO Genset stopped in Auto
MPE ACTIVE Genset running in mains power export mode
DG BLOCKED FOR
START
Generator stopped and active alarm(s) on the gener-
ator
GB ON BLOCKED Generator running, GB open and an active "Trip GB"
alarm
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 14 of 24