Condition Comment
START RELAY OFF The start relay is deactivated during the start se-
quence
MAINS FAILURE Mains failure and mains failure timer expired
MAINS FAILURE IN ###s Frequency or voltage measurement is outside the lim-
its
The timer shown is
the Mains failure de-
lay.Text in mains
units
MAINS U OK DEL ####s Mains voltage is OK after a mains failure The timer shown is
the Mains OK delay
MAINS f OK DEL ####s Mains frequency is OK after a mains failure The timer shown is
the Mains OK delay
Hz/V OK IN ###s The voltage and frequency on the genset is OK When the timer runs
out it is allowed to op-
erate the generator
breaker
COOLING DOWN ###s Cooling-down period is activated
COOLING DOWN Cooling-down period is activated and infinite Cooling down timer is
set to 0.0 s
GENSET STOPPING This info is shown when cooling down has finished
EXT. STOP TIME ###s
EXT. START ORDER A planned AMF sequence is activated There is no failure on
the mains during this
sequence