Table 21. Relative humidity specications
Relative humidity Specications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be
non-condensing at all times.
Operating 10% to 80% relative humidity with 26°C (78.8°F) maximum dew point.
Table 22. Maximum vibration specications
Maximum vibration Specications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage 1.87 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Table 23. Maximum shock specications
Maximum shock Specications
Operating One shock pulse in the positive z axis of 40 G for 2.3 ms in all operational
orientations.
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Table 24. Maximum altitude specications
Maximum altitude Specications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 25. Operating temperature de-rating specications
Operating temperature de-rating Specications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specied limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.