Q In C/CP2000 and MS300: What is the difference between M1042 Quick Stop and
M1044 Pause in the PLC?
A Quick Stop M1042 = 1: Drive will stop with the shortest possible deceleration ramp.
M1042 = 0: Drive start enabled. The drive will not restart by itself.
Pause M1044 = 1: The drive will stop with the normal deceleration ramp.
M1044 = 0: The drive will resume the previous operation with the normal
acceleration ramp. The user does not need to restart.
Q How can I read drive series and model by serial communication?
A Read address 2110hex.
Series Code 2110h High byte 2110h Low byte Type
C2000 20 14h
FFh
Read ID in
Pr00-00
(Address 000h)
CP2000 21 15h
CH2000 22 16h
C200 25 19h
CT2000 30 1Eh
CFP2000 42 2Ah
MH300 31 1Fh
MS300 32 20h
ME300 33 21h
MH300-L 48 30h
C2000HS 49 31h
MH300HS 51 33h
MS300HS 52 34h