Q Bug: Pr09-02 and Pr09-03 do not work.
A When Pr09-02=1 or 2 and Pr09-03=1s (or other value), when the drive communication
is interrupted (by pulling the connector for example, nothing happens. Acc. to manual
the drive should stop after Pr09-03 time. But it doesnt work.
Q Why does VFD-L2 show cF2 after power on?
A When the value of Pr07-01 > Pr07-00 this will happen. Normally it is not a problem
but when you set a full load current value in Pr07-00 that is lower than the no-load
current value in Pr07-01, this problem occurs. The solution is to make sure that Pr07-
01 < Pr07-00.
Q Why is EF (fault code 6) not saved in the fault memory?
A This is a bug in the firmware. At the moment, there are no plans to correct it.
Q How can I set the delay between Autorestarts?
A Autorestart only works for OC and OV.
Number of Autorestarts Pr8-14
Autorestart Recovery Time PrA-15 (hidden parameter)
To change the hidden parameter, set Pr0-02=2, then go to Pr-group A and change the
setting in PrA-15. Default is 10min.
Q What is the difference among A, B, D and E versions of VFD-L?
A A: No filter, NPN inputs
B: Filter, NPN inputs
D: No filter, PNP inputs (only for 0.4 and 0.75kW)
E: Filter, PNP inputs (only for 0.4 and 0.75kW)
Q Can the relay be used on 230VAC?
A Yes, it can be used to switch 230V
AC
with a max. current of 1A.