EasyManua.ls Logo

Delta Electronics AC Motor Drive VFD-EL - Page 54

Delta Electronics AC Motor Drive VFD-EL
209 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameters|
Revision August 2008, 2ELE, V1.02 4-11
Parameter Explanation Settings
Factory
Setting
Customer
04.15
Min ACI Current 0.0 to 20.0mA
4.0
04.16
Min ACI Frequency
0.0 to 100.0%
0.0
04.17
Max ACI Current 0.0 to 20.0mA
20.0
04.18
Max ACI Frequency 0.0 to 100.0%
100.0
04.19
|
04.25
Reserved
Read only.
Bit0: MI1 Status
Bit1: MI2 Status
Bit2: MI3 Status
Bit3: MI4 Status
Bit4: MI5 Status
04.26
Display the Status
of Multi-function
Input Terminal
Bit5: MI6 Status
##
04.27
Internal/External
Multi-function Input
Terminals Selection
0~4095
0
04.28
Internal Terminal
Status
0~4095
0
Group 5 Multi-Step Speed Parameters
Parameter Explanation Settings
Factory
Setting
Customer
05.00 1st Step Speed
Frequency
0.00 to 600.0 Hz 0.00
05.01 2nd Step Speed
Frequency
0.00 to 600.0 Hz 0.00
05.02 3rd Step Speed
Frequency
0.00 to 600.0 Hz 0.00
05.03 4th Step Speed
Frequency
0.00 to 600.0 Hz 0.00
05.04 5th Step Speed
Frequency
0.00 to 600.0 Hz 0.00

Table of Contents