Chapter 6 Technical Specications
Chapter 6 : Technical Specications
Model 1K 2K 3K
Capacity
1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W
Input
Voltage Range 110-300Vac*
Frequency Range 40Hz ~ 70Hz
Phase Single phase with ground
Power Factor
≧
0.99 @ nominal voltage (Input Voltage)
Output
Nominal voltage 200**/208**/220/230/240 Vac
Voltage Regulation ±1% (Batt. Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range
(Batt. Mode)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Overload
Ambient Temp.<35°C
105% ~ 110%: The UPS shuts down after 10 minutes in bat-
tery mode or transfers to bypass when the utility is normal.
110% ~ 130%: The UPS shuts down after 1 minute in battery
mode or transfers to bypass when the utility is normal.
>130%: The UPS shuts down after 3 seconds in battery
mode or transfers to bypass when the utility is normal.
Current Crest Ratio 3:1
Harmonic Distortion
≦
3 % THD (linear load);
≦
6 % THD (non-linear load)
Waveform
(Batt. Mode)
Pure Sinewave
Efciency
AC Mode 88% 89% 90%