EasyManuals Logo

Delta Elektronika SM 3000 Series User Manual

Delta Elektronika SM 3000 Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
SM3000 DELTA ELEKTRONIKA BV
1991, rev. May 2008 OPERATING MAINTENANCE TROUBLE SHOOTING CALIBRATING Page 4 - 3
Note: The SM300-10D needs an ex tra par allel di ode on the
output, without this di ode the in ternal di ode will still blow. For
this di ode 2 par alleled BYT261-PIV-400 from ST can be used.
The SM300-10D with op tion P023 has an extra di ode built-in.
8)
REMOTE SHUT DOWN / OVER CUR RENT TRIP
The Remote ShutDown can be op erated with +5 V or a re lay
contact (see fig. 4 - 10).
Using the Remote ShutDown in put, an Over Cur rent Trip
could be made (see fig. 4 - 10).
9) MASTER / SLAVE SERIES OP ERATION
For se ries op er a tion the MAS TER / SLAVE SE RIES ADAP-
TER
(δ-prod uct) must be used (see fig. 4 - 11).
First, connect output terminals and test sys tem in nor mal se-
ries op eration. Ensure that all (out put) power con nections are
reliable. An in terruption of one of the power leads can cause a
fuse to blow in the unit, see ''trou ble shoot ing''.
The voltage drop in the con necting leads be tween the units
should be kept < 10 mV.
Second, switch off all units. Con nect units as shown in fig. 4 -
12. Use standard 15 pole (1:1) shielded ca bles.
The max. num ber of slaves is only limited by the max. total volt-
age of 600 V.
10)
MASTER / SLAVE PAR AL LEL OP ER A TION
Note: Master / Slave parallel is not recommended for more
than 4 units, con sult factory for us ing more than 4 power
sup plies in par al lel.
First con nect output terminals and test sys tem in nor mal par al-
lel op eration. Ensure that all power con nections are reliable. An
interruption of one of the (output) power leads can cause a fuse
to blow in the unit, see “trou ble shoot ing”.
Second, switch off all units. Plug in prog. connectors with the
con nec tions ac cord ing to fig. 4 - 13 (buss bar to pology). Always
use a shielded ca ble. The shielding must be connected to the
case of the supply.
Disconnect the links be tween the S– and – of the slaves only.
If not re moved the current sharing will not be pro portional.
Both prog. switches of the slaves should be in the po sition PRO-
GRAM.
The pur pose of the link be tween pin 9 and 11 is to set the volt -
age limit of the slaves at max imum.
Keep the load close to the master. Keep wir ing be tween mas ter
and slaves short. The voltage drop be tween a unit and the buss
bar should be kept < 10 mV.
Accidental in terruption of a neg ative load lead of a unit dur ing
operation will cause fuse F600 to blow, see sec tion ‘trouble
shoot ing’.
The S and S+ could be connected to the load if de sired, but this
is not recommended be cause of the com plexity.
fig. 4 - 10
Left: Remote ShutDown with switch.
Right: Over Current Trip
fig 4 - 11
The Master / Slave Series Adapter,
supplied by Delta Elektronika
fig. 4 - 12
Master / Slave Series Connection with
two MASTER / SLAVE SERIES ADAPTERS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Elektronika SM 3000 Series and is the answer not in the manual?

Delta Elektronika SM 3000 Series Specifications

General IconGeneral
BrandDelta Elektronika
ModelSM 3000 Series
CategoryPower Supply
LanguageEnglish

Related product manuals