EasyManua.ls Logo

Delta Elektronika SM 70-90 - SW1 Function Switches

Delta Elektronika SM 70-90
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM6000 DELTA ELEKTRONIKA BV
July 2003, rev. May 2008 DESCRIPTIONS Page 3 - 3
The Cur rent Con trol Status or CC-status out put is "1" when the unit is in
CC-mode.
The Power Sink Over Load Sta tus or PSOL-status out put is "1" when the op tional
Power Sink is over loaded or over heated.
The AC-Fail Sta tus or ACF-sta tus out put is "1" in case of Phase Loss or when the
input voltage is be low 340 V.
The DC-Fail Sta tus or DCF-sta tus out put is "1" when the out put voltage is ei ther
5% be low or above the set point.
When the unit is in CC-mode, DCF will al ways be "1", see pre vious para graph 7).
15)
STATUS RE LAY OUT PUTS
The power supply has 2 status re lay out puts, with each a change-over contact.
They are connected to con nector CON D. The pins 1,2,3 are con nected to the
DCF-relay and pins 4,5,6 to the ACF-relay (see fig. 3 - 10).
16)
FUNCTION SWITCHES ON SW1
In the following ta ble the functions of the DIP switches 1-4 of switch SW1 (rear
side) are explained:
fig. 3 - 8 Location of out put terminals and an alog prog. con nector on rear panel
Switch no. ON po si tion OFF po si tion De fault Set ting
SW 1 - 1 Pro gramming via 15pole con nec-
tor CON E (an alog).
Op tional pro gram ming with e.g.
PSC-232, PSC-488, ISO AMP CARD
ON (up)
SW 1 - 2 ‘Output On’ af ter mains on ‘Output Off’ af ter mains on OFF (down)
SW 1 - 3 DCF LED enabled DCF LED dis abled (DCF sta tus and
DCF re lay are still en abled)
ON (up)
SW 1 - 4 Parallel Mas ter / Slave operation Series Mas ter / Slave operation ON (up)
CON A In ter lock Con nec tor
CON B Master connector for Mas ter / Slave op eration (out put)
CON C Slave con nector for Mas ter / Slave op eration (in put)
CON D Relay Out puts, con tacts 1 - 6
CON E An a log Pro gramming Connector
CON F PSC-232, from PC or pre vious PSC (op tional)
CON G PSC-232, to next PSC (op tional)
CON H PSC-488 (op tional) or
ISO AMP CARD (optional)
SW 1 Var i ous set tings, see para graph 16)
SW 2 Set tings for PSC-488 and PSC-232 (op tional)
fig. 3 - 9 Connectors and switches on the rear panel
fig. 3 - 10
Status relay outputs on CON D.
This sit uation gives the relay
po si tions dur ing fault con di tion.

Other manuals for Delta Elektronika SM 70-90

Related product manuals