EasyManuals Logo

Delta ASD-M-0721-F User Manual

Delta ASD-M-0721-F
645 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
ASDA-M Chapter 6 Control Mode of Operation
Revision December, 2014
6-19
value of P1-26 and P1-28 is 0, it means no frequency has been detected. Please
decrease the value of P1-30 and set P1-29 to 1 so as to search the vibration frequency
again. Please note that when the detection level is set too small, the noise will be
regarded as the low-frequency.
Flowchart of auto low-frequency vibration suppression:
Note 1: When the value of P1-26 and P1-28 is 0, it means it is unable to search the
frequency. It is probably because the detection level is set too high and is unable
to detect the low-frequency vibration.
Note 2: When the value of P1-26 or P1-28 is not set to 0 and still cannot eliminate the
vibration, it is probably because the detection level is set too low, the system
regards the noise or other non-primary frequency as the low-frequency vibration.
Note 3: When the process of auto vibration suppression is completed and the vibration
still cannot be diminished, P1-25 or P1-27 can be manually set to suppress the
vibration if the frequency (Hz) of the low-frequency is identified.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASD-M-0721-F and is the answer not in the manual?

Delta ASD-M-0721-F Specifications

General IconGeneral
BrandDelta
ModelASD-M-0721-F
CategoryServo Drives
LanguageEnglish

Related product manuals