Chapter 11 Description of Parameter Settings|C200 Series
11-23
0
01-28
01-29
01-30
01-31
01-32
01-33
Internal
frequency
command
Frequency setting command
rising frequency
falling fr eq ue ncy
Zero-speed Mode
Factory Setting: 0
Settings
0: Output waiting
1: Zero-speed operation
2: Fmin (4
th
output frequency setting)
When the frequency is less than Fmin (Pr.01-07 or Pr.01-41), it will operate by this parameter.
When it is set to 0, the AC motor drive will be in waiting mode without voltage output from terminals
U/V/W.
When setting 1, it will execute DC brake by Vmin. (Pr.01-08 and Pr.01-42) in V/f, VFPG and SVC
modes. It executes zero-speed operation in VFPG and FOCPG mode.
When it is set to 2, the AC motor drive will run by Fmin (Pr.01-07, Pr.01-41) and Vmin (Pr.01-08,
Pr.01-42) in V/f, VFPG, SVC and FOCPG modes.
In V/f, VFPG and SVC modes
fmin
01-07
fout
0Hz
01-34=0
01-34=2
01-34=1
0Hz
stop output
0Hz operation
(DC brake)
stop waiting for output
In FOCPG mode, when Pr.01-34 is set to 2, it will act according Pr.01-34 setting.
fmin
01-07
fout
01-34=0
01-34=2
01-34=1
frequency command
frequency command
V/f Curve Selection
Factory Setting: 0
Settings 0: V/f curve determined by group 01
1: 1.5 power curve
2: Square curve