Chapter 11 Description of Parameter Settings|C200 Series
11-99
Settings
0 : No function
1 : warn and coast to stop
2 : warn and ramp to stop by 2
nd
deceleration time
3 : warn and operation continue
The drive will operate as the setting of Pr.06-73 when output current is lower than the setting of
Pr.06-71 and when low current continues for a period longer than the setting of Pr.06-72. This
parameter can also be used with external multi-function output terminal 44 (MO44) for low current
output.