Chapter 11 Description of Parameter Settings|C200 Series
11-131
CANopen Decoding Method
Factory Setting: 1
Settings 0: Delta defined decoding method
1: CANopen Standard DS402 protocol
CANopen Status
Factory Setting: 0
Settings 0: Node Reset State
1: Com Reset State
2: Boot up State
3: Pre Operation State
4: Operation State
5: Stop State
CANopen Control Status
Factory Setting: Read Only
Settings 0: Not ready for use state
1: Inhibit start state
2: Ready to switch on state
3: Switched on state
4: Enable operation state
7: Quick stop active state
13: Err reaction activation state
14: Error state
Reset CANopen Index
Factory Setting: 65535
Settings:
bit0: reset address 20XX to 0.
bit1: reset address 264X to 0
bit2: reset address 26AX to 0
bit3: reset address 60XX to 0
CANopen Error state
Factory Setting: Read Only
Settings 0~65535