Chapter 5 Main Circuit Terminals|C200 Series
5-4
5-1 Main Circuit Terminals
Frame A0
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , DC+, DC-, B1, B2
Models
Max. Wire
Gauge
Min. Wire Gauge
Torque
(±10%)
VFD004CB21A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD007CB21A-20/-21/-21M 12 AWG (3.3mm
2
)
VFD015CB21A-20/-21/-21M 10 AWG (5.3mm
2
)
VFD022CB21A-20/-21/-21M 8 AWG (8.4mm
2
)
VFD004CB23A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD007CB23A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD015CB23A-20/-21/-21M 12 AWG (3.3mm
2
)
VFD022CB23A-20/-21/-21M 10 AWG (5.3mm
2
)
VFD037CB23A-20/-21/-21M 8 AWG (8.4mm
2
)
VFD007CB43A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD015CB43A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD022CB43A-20/-21/-21M 14 AWG (2.1mm
2
)
VFD037CB43A-20/-21/-21M
8 AWG
(8.4mm
2
)
10 AWG (5.3mm
2
)
M4
20kg-cm
(17.4 lb-in.)
(1.96Nm)
UL installations must use 600V, 75 or 90 wire. Use copper wire only.
NOTE
Figure 1 shows the terminal specification.
Figure 2 shows the specification of insulated heat shrink tubing that comply with UL
(600V, YDPU2).
Figure 1 Figure 2