Chapter 14 PLC Function |C200 Series
14-61
API
240~
246
D
OR
S1 S2
OR Compare
Bit Devices Word Devices
X Y M K H KnX KnY KnM T C D
S
1
S
2
Operands: : =, >, <, <>,,
Please refer to the specifications of each model for the
range of operands.
16-bit command (5 STEPS)
OR
ZRSTP
32-bit command (9 STEPS)
DOR
Flag signal: none
Explanation
1. S
1
: Data source device 1 S
2
: Data source device 2
2. This instruction compares the content in S
1
and S
2
. Take API240 (OR=) for
example, if the result is “=”, the continuity of the instruction is enabled. If the
result is “”, the continuity of the instruction is disabled.
3. OR ( : =, >, <, <>, , ) is an comparison instruction used on parallel
contacts.
API No.
16 -bit
instruction
32 -bit
instruction
Continuity
condition
No-continuity
condition
232
AND DAND S
1
S
2
S
1
S
2
233
AND DAND S
1
S
2
S
1
S
2
234
AND DAND S
1
S
2
S
1
S
2
236
AND<> DAND<>
S
1
S
2
S
1
S
2
237
AND<= DAND<=
S
1
S
2
S
1
S
2
238
AND>= DAND>=
S
1
S
2
S
1
S
2
Example
1. When X1 = On and the present value of C10 = K200, Y0 = On.
2. When X1 = Off and the content in D0 K-10, Y11= On will be retained.
3. M50 will be On when X2=On and the content of 32-bit register D0(D11) <678,493
or M3= On.
AND=
K200 C10
DAND>
K678493 D10
M3
Y10
AND<>
K-10 D0
SET Y11
M50
X2
X1
X0