Chapter 8 Specification |C200 Series
8-1
Chapter 08 Specification
230V Series -1 Phase
Frame Size A0
Model VFD -_ _ _CB21A-_ _ _
*1
004 007 015 022
Applicable Motor Output (kW)
0.4 0.75 1.5 2.2
Applicable Motor Output (HP)
0.5 1 2 3
Rated Output Capacity (kVA) 1.2 2.0 3.2 4.4
Rated Output Current (A) 3 5 8 11
Overload Tolerance
rated output current is 120% for 60 seconds;
rated output current is 160% for 3 seconds
Max. Output Frequency (Hz) 600.00Hz
NORMAL
DUTY
Carrier Frequency (kHz) 2~15kHz (Factory Setting: 8 kHz)
Rated Output Capacity (kVA) 1.1 1.9 2.8 4.0
Rated Output Current (A) 2.8 4.8 7.1 10
Overload Tolerance
rated output current is 150% for 60 seconds;
rated output current is 180% for 3 seconds
Max. Output Frequency (Hz) 600.00Hz
Output Rating
HEAVY
DUTY
Carrier Frequency (kHz) 2~15kHz (Factory Setting: 2 kHz)
Input Current (A) Normal Duty
7.2 12 15.7 22
Input Current (A) Heavy Duty 6.7 11.5 14 20
Rated Voltage/Frequency AC 200V~240V (-15% ~ +10%), 50/60Hz, 1-Phase
Operating Voltage Range 170~265Vac
Input
Rating
Frequency Tolerance 47~63Hz
Cooling method Natural cooling Fan cooling
Braking Chopper Built-in
230V Series -3 Phase
Frame Size A0
Model VFD -_ _ _CB23A-_ _ _
*1
004 007 015 022 037
Applicable Motor Output (kW)
0.4 0.75 1.5 2.2 3.7
Applicable Motor Output (HP)
0.5 1 2 3 5
Rated Output Capacity (kVA) 1.2 2.0 3.2 4.4 6.8
Rated Output Current (A) 3 5 8 11 17
Overload Tolerance
rated output current is 120% for 60 seconds;
rated output current is 160% for 3 seconds
Max. Output Frequency (Hz) 600.00Hz
NORMAL
DUTY
Carrier Frequency (kHz) 2~15kHz (Factory Setting: 8 kHz)
Rated Output Capacity (kVA) 1.1 1.9 2.8 4.0 6.4
Rated Output Current (A) 2.8 4.8 7.1 10 16
Overload Tolerance
rated output current is 150% for 60 seconds;
rated output current is 180% for 3 seconds
Max. Output Frequency (Hz) 600.00Hz
Output Rating
HEAVY
DUTY
Carrier Frequency (kHz) 2~15kHz (Factory Setting: 2 kHz)
Input Current (A) Normal Duty
3.9 6.4 12 16 20
Input Current (A) Heavy Duty 3.6 6.1 11 15 18.5
Rated Voltage/Frequency AC 200V~240V (-15% ~ +10%), 50/60Hz 3-Phase
Operating Voltage Range 170~265Vac
Input
Rating
Frequency Tolerance 47~63Hz
Cooling method Natural cooling Fan cooling
Braking Chopper Built-in