Chapter 10 Summary of Parameter Settings|C200 Series
10-12
Parameter Explanation Settings
Factory
Setting
03-23
Multi-function Output 2
(AFM2)
1: Frequency command (Hz) 0
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current
13: Iq feedback value
14: Id current
15: Id feedback value
16: Vq-axis voltage
17: Vd-axis voltage
18: Torque command
19: Reserved
20: CANopen analog output
21: RS485 analog output
22: Reserved
23: Constant voltage/current output
03-21
Gain of Analog Output 1
(AFM1)
0~500.0% 100.0
03-22
Analog Output 1 when in
REV Direction (AFM1)
0: Absolute output voltage
1: Reverse output 0V; Positive output 0-10V
2: Reverse output 5-0V; Positive output 5-10V
0
03-24
Gain of Analog Output 2
(AFM2)
0~500.0% 100.0
03-25
Analog Output 2 when in
REV Direction (AFM2)
0: Absolute output voltage
1: Output 0V in REV direction; output 0-10V in FWD
direction
2: Output 5-0V in REV direction; output 5-10V in FWD
direction
0
03-26 Reserved
03-27 Reserved
03-28 AVI Selection
0: 0-10V
1: 0-20mA
2: 4-20mA
0
03-29 ACI Selection
0: 4-20mA
1: 0-10V
2: 0-20mA
0
03-30
Status of PLC Output
Terminal
Monitor the status of PLC output terminals
Read
only
03-31
AFM2 0-20mA Output
Selection
0: 0-20mA Output
1: 4-20mA Output
0
03-32
AFM1 DC output setting
level
0.00~100.00% 0.00
03-33
AFM2 DC Output Setting
Level
0.00~100.00% 0.00
03-34
~
03-38
Reserved
03-39
keypad potentiometer
Selection
0: No function
1: Frequency command
0
03-40
keypad potentiometer
Input Bias
-100.0~100.0% 0.0