Chapter 10 Summary of Parameter Settings|C200 Series
10-18
06 Protection Parameters
Parameter Explanation Settings
Factory
Setting
06-00 Low Voltage Level
230V: 150.0~220.0Vdc
460V: 300.0~440.0Vdc
180.0
360.0
06-01
Over-voltage Stall
Prevention
0: Disabled
230V: 0.0~450.0Vdc
460V: 0.0~900.0Vdc
380.0
760.0
06-02
Selection for Over-voltage
Stall Prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
0
06-03
Over-current Stall
Prevention during
Acceleration
Normal Load: 0~160%(100%: drive’s rated current)
Heavy Load: 0~180%(100%: drive’s rated current)
120
150
06-04
Over-current Stall
Prevention during
Operation
Normal Load: 0~160%(100%: drive’s rated current)
Heavy Load: 0~180%(100%: drive’s rated current)
120
150
06-05
Accel. /Decel. Time
Selection of Stall
Prevention at Constant
Speed
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0
06-06
Over-torque Detection
Selection (OT1)
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operate after detection
4: Over-torque detection during operation, stop
operation after detection
0
06-07
Over-torque Detection
Level (OT1)
10~250% (100%: drive’s rated current) 120
06-08
Over-torque Detection
Time (OT1)
0.0~60.0 sec. 0.1
06-09
Over-torque Detection
Selection (OT2)
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop
operation after detection
0
06-10
Over-torque Detection
Level (OT2)
10~250% (100%: drive’s rated current) 120
06-11
Over-torque Detection
Time (OT2)
0.1~60.0 sec. 0.1
06-12 Current Limit
0~250% (100%: drive’s rated current
150
06-13
Electronic Thermal Relay
Selection (Motor 1)
0: Inverter motor
1: Standard motor
2: Disable
2
06-14
Electronic Thermal
Characteristic for Motor 1
30.0~600.0 sec. 60.0
06-15
Heat Sink Over-heat (OH)
Warning
0.0~110.0 85.0
06-16
Stall Prevention Limit
Level
0100% (Pr.06-03, Pr.06-04)
50
06-17 Present Fault Record 0: No fault record 0
06-18
Second Most Recent Fault
Record
1: Over-current during acceleration (ocA) 0