EasyManua.ls Logo

Delta DPM-C510 - 5.1 Overview of Parameters

Delta DPM-C510
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi-functional Power Meter DPM-C510 Operation Manual
5-2
_5
5.1 Overview of Parameters
Modbus
Address
Item Range
Data
Type
Unit
Data
Size
(byte)
Read (R) /
Write (W)
Hex
Modicom
Format
0. System Parameters: 0001 00FF
5 40006 Meter Constant 3200 uint P/kWh 2 R
6 40007 Meter Model
0: None
4: DMPC510
word
2 R
7 40008
Total running time of the
meter
0 ~ 4294967295
uint Minute 4 R
8 40009
9 40010 Firmware version
0.00 ~ 9.99 word
2 R
A 40011
Firmware release date
Year: 0099
Month: 112
byte
Year,
Month
2 R
B 40012 Date: 131 word Date 2 R
C 40013 Reserved
D 40014
Power system
configuration
0: 3φ4W
1: 3φ3W
2: 1φ2W
3: 1φ3W
word
2 R/W
E 40015 Primary CT (A) 1 9999 uint A 2 R/W
F 40016 Secondary CT (A)
0: 1A
1: 5A
word A 2 R/W
10 40017 Primary PT
1 ~ 65534 uint V 2 R / W
11 40018 Secondary PT
1 ~ 9999 uint V 2 R / W
13 40020 Reserved
14 40021
Backlight delay
*For model C501L, this
function is only
supported by firmware
V1.006 and above.
0 – 99
0: Backlight remains OFF.
99: Backlight remains ON.
word Second
2 R/W
15 40022 Reserved