Multi-functional Power Meter DPM-C510 Operation Manual
5-2
5.1 Overview of Parameters
Modbus
Address
Item Range
Data
Type
Unit
Data
Size
(byte)
Read (R) /
Write (W)
Hex
Modicom
Format
0. System Parameters: 0001 – 00FF
5 40006 Meter Constant 3200 uint P/kWh 2 R
6 40007 Meter Model
0: None
4: DMP–C510
word
2 R
7 40008
Total running time of the
meter
0 ~ 4294967295
uint Minute 4 R
8 40009
9 40010 Firmware version
0.00 ~ 9.99 word
2 R
A 40011
Firmware release date
Year: 00–99
Month: 1–12
byte
Year,
Month
2 R
B 40012 Date: 1–31 word Date 2 R
C 40013 Reserved
D 40014
Power system
configuration
0: 3φ4W
1: 3φ3W
2: 1φ2W
3: 1φ3W
word
2 R/W
E 40015 Primary CT (A) 1 – 9999 uint A 2 R/W
F 40016 Secondary CT (A)
0: 1A
1: 5A
word A 2 R/W
10 40017 Primary PT
1 ~ 65534 uint V 2 R / W
11 40018 Secondary PT
1 ~ 9999 uint V 2 R / W
13 40020 Reserved
14 40021
Backlight delay
*For model C501L, this
function is only
supported by firmware
V1.006 and above.
0 – 99
0: Backlight remains OFF.
99: Backlight remains ON.
word Second
2 R/W
15 40022 Reserved