23
15 Screen brightness
0: 100%
1: 50%
2: 25%
byte 1 R / W
16 Baud Rate
0: 9600,
1: 19200,
2: 38400
byte bps 1 R / W
17 Communication mode
0: ASCII
1: RTU
byte 1 R / W
18 Data bit
0: 8
1: 7
byte 1 R / W
19 Parity
0: None
1: Even
2: Odd
byte 1 R / W
1A Stop bit
0: 1
1: 2
byte 1 R / W
1B Meter address 0 ~ 255 byte 1 R / W
1C Reset parameters on meter
0: None
1: Reset factory default
2: Reset value of energy
3: Reset value of demand
4: Clear alarm logs and times
5: Reset maximum and minimum values
6: Clear saved logs
7: Clear all values
byte 1 W
1D Demand (method of calculation) 0: block byte 1 R
1E Time interval for demand (min) 0 ~ 60 byte minute 1 R / W
Alarm - Over Current
1F Alarm Enable
0: Disable
1: Enable
byte 1 R / W
20
Pickup setpoint (currents
exceeding this value(A), alarm
generated)
0.000~99999.999 Float
A 4 R / W
21
22
Pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
23
Dropout setpoint (currents lower
than this value (A), alarm cleared)
0.000~99999.999 Float A 4 R / W
24
25
Dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Under Current
26 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
27
Pickup setpoint (currents lower
than this value (A), alarm
generated)
0.000~99999.999 Float A 4 R / W
28
29
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
2A
Dropout setpoint (currents
exceeding this value (A), alarm
cleared)
0.000~99999.999 Float A 4 R / W
2B
2C
Dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Over Neutral Current
2D Alarm Enable
0: Disable
1: Enable
byte 1 R / W