24
2E
Pickup setpoint (currents
exceeding this value(A), alarm
generated
 
0.000~99999.999 Float A 4 R / W
2F
30
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
31
Dropout setpoint (currents lower
than this value (A), alarm cleared)
0.000~99999.999 Float A 4 R / W
32
33
Dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Over Line Voltage
34 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
35
pickup setpoint (voltage
exceeding this value (V), alarm
generated)
0.000~99999.999 Float V 4 R / W
36
37
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
38
dropout setpoint (voltage lower
than this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
39
3A
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Under Line Voltage
3B Alarm Enable
0: Disable
1: Enable
byte 1 R / W
3C
pickup setpoint (voltage lower
than this value (V), alarm
generated)
0.000~99999.999 Float V 4 R / W
3D
3E
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
3F
dropout setpoint (voltage
exceeding this value (V), alarm
cleared)
0.000~99999.999 Float V 4 R / W
40
41
dropout time delay (restoration
delayed)
0~99 byte s 2
R / W
Alarm - Over Phase Voltage
42 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
43
pickup setpoint (voltage
exceeding this value (V), alarm
generated)
0.000~99999.999 Float V 4 R / W
44
45
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
46
dropout setpoint (voltage lower
than this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
47
48
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Under Phase Voltage
49 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
4A
pickup setpoint (voltage lower
than this value (V), alarm
generated)
0.000~99999.999 Float V 4 R / W