DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
3-390
Number
Description
Remark
to other codes.
S
2
+3 Communication data length
It is used to set the length of the data
read/written. A word is a unit of measurement
for length. The maximum number of words
which can be read/written is 16.
S
2
+0: Communication combination function code
Function
code
Attribute
#1
Function
K0 R or W
There is no communication combination. Users can define a DMV
communication command. Please refer to DMO Module Manual for
more information about the registers which can be read/written. The
data read/written are stored in the devices starting from D
1
.
K1 W and R
Communication combination commands sent to a DMV
#2
:
1) DMV trigger 1 is enabled.
2) The value in S
2
+3 indicates the number of data read from the
output data area in a DMV.
(The maximum number of words which
can be read is 16.) The data read is stored in the devices starting
from D
1
.
K2 W
Communication combination commands sent to a DMV:
1) The DMV program number indicated by the value in D
1
is used.
(The value in D
1
is in the range of 0 to 31.)
2) DMV trigger 1 is enabled.
K3 W and R
Communication combination commands sent to a DMV:
1) The DMV program number indicated by the value in D
1
is used.
(The value in D
1
is in the range of 0 to 31.)
2) DMV trigger 1 is enabled.
3) The value in S
2
+3 indicates the number of data read from the
output data area in a DMV.
(The maximum number of words which
can be read is 16.) The data read is stored in the devices starting
from D
1
.
K4 W
Communication combination commands sent to a DMV:
1) The values in D
1
+0 and D
1
+1 are written into internal memory 1.
2) DMV trigger 1 is enabled.
K5 W and R
Communication combination commands sent to a DMV:
1) The values in D
1
+0 and D
1
+1 are written into internal memory 1.
2) DMV trigger 1 is enabled.
3) The value in S
2
+3 indicates the number of data read from the
output data area in a DMV.
(The maximum number of words which
can be read is 16.) The data read is stored in the devices starting
from D
1
.
K6 W
Communication combination commands sent to a DMV:
1) The values in D
1
+0 and D
1
+1 are written into internal memory 2.
2) DMV trigger 1 is enabled.
K7 W and R
Communication combination commands sent to a DMV:
1) The values in D
1
+0 and D
1
+1 are written into internal memory 2.
2) DMV trigger 1 is enabled.
3) The value in S
2
+3 indicates the number of data read from the
output data area in a DMV.
(The maximum number of words which
can be read is 16.) The data read is stored in the devices starting
from D
1
.
Note
#1
: W and R mean that a writing communication command is executed first, and then a
reading communication command is executed. If the function code used is K3, the D operand