EasyManua.ls Logo

Delta DVP-ES2 - Page 956

Delta DVP-ES2
1006 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appedndix B Setting and Using an Ethernet PLC/Module
B-23
3. Use DCISoft for DVP-SE to set start addresses and numbers. (RX: M2000~M2009; RY:
M3000~M3009; RCR (Reading): D2000~D2009; RCR (Writing): D3000~D3009)
4. Edit a ladder diagram, and download it to DVP-SE. The program edited is like the one shown
below.
Description:
(1) Enabling mapping: CR15=1
(2) Disabling mapping: CR15=0
(3) After CR#15 is enabled, M2000~M2009 and D2000~D2009 will be used to read data, and
present values will be read before M3000~M3009 and D3000~D3009 are used to write
data.
During the execution of mapping, other devices can not be used to modify the values in
mapping registers.
If DVPEN01-SL is used, K108 will be changed to the number assigned to DVPEN01-SL. If
DVPEN01-SL is the first module connected to the left side of a PLC, K108 will be changed
to K100.

Table of Contents

Other manuals for Delta DVP-ES2

Related product manuals